The CS141 provides integrated watchdog protection that restarts individual services or the CS141 / BACS in the event of problems. If this fails, additional administrative options are available to restart manually. The UPS is not affected by this restart.
In case a login is still available:
Open System>Tools, and click on „Reboot“. The CS141 will restart with a soft boot. After booting, you will be forwarded to the login dialogue. The UPS system is not harmed and will stay online.
In case the login is no longer possible, but the CS141 will react somehow:
At the URL-address bar of your web browser, enter: „http(s)://<IP-Address>/reboot“
This will trigger the soft reboot without a login via the dialogue. Since the restart is a system-critical process, the administrator password (user admin) is required.
http://<IP-Address>/backup
This feature directly triggers the backup function, bypassing the standard login. The CS141 will directly create and provide a backup for download. Since this is a system-critical operation, a valid administrator password is requested before download starts.
http://<IP-Address>/update
This option allows administrators to distribute a system update directly and reset the configuration file to factory default.
Use Drag&Drop to place the file or click on „click to select“ to open a file manager. Since this is an emergency option, the configuration file will be deleted and the CS141 will fall back to factory default settings. Due to the fact the device may be located hard to reach physically, IP address reset is processed separately and on demand only.
To start the flash procedure, enter the username admin and the corresponding password.
Note:
Network settings and system settings are separated from each other to allow a flash update on demand that includes deleting all system settings without losing the IP address data.