| Address | Type | Function | Name | Description | Length |
| 97 | U | 3 / 4 | OUTPUT_VOLT0 | Output Voltage Phase 1 in V | 1 |
| 98 | U | 3 / 4 | OUTPUT_VOLT1 | Output Voltage Phase 2 in V | 1 |
| 99 | U | 3 / 4 | OUTPUT_VOLT2 | Output Voltage Phase 3 in V | 1 |
| 100 | U | 3 / 4 | OUTP0WER0 | Outpower Phase 1 % | 1 |
| 101 | U | 3 / 4 | OUTP0WER1 | Outpower Phase 2 % | 1 |
| 102 | U | 3 / 4 | OUTP0WER2 | Outpower Phase 3 % | 1 |
| 103 | U | 3 / 4 | BATTCAP | Battery Capacity % | 1 |
| 104 | S | 3 / 4 | INVOLT0 | Input Voltage Phase 1 V | 1 |
| 105 | S | 3 / 4 | INVOLT1 | Input Voltage Phase 2 V | 1 |
| 106 | S | 3 / 4 | INVOLT2 | Input Voltage Phase 3 V | 1 |
| 107 | S | 3 / 4 | TEMPDEG | Temperature C° | 1 |
| 108 | S | 3 / 4 | AUTONOMTIME | Autonomy Time minutes | 1 |
| 109 | U | 3 / 4 | STATUS (e. g. UPS normal = “4”, Powerfail = “12”, Battery test running = “68”, Bypass = “5” ) | UPS Status (ASCII HEX) Please note UPSMAN status bytes table below | 1 |
| 110 | S | 3 / 4 | BATTVOLT | Battery Voltage V | 1 |
| 111 | U | 3 / 4 | INFREQ0 | Input Frequency Hz Phase 1 | 1 |
| 112 | U | 3 / 4 | INFREQ1 | Input Frequency Hz Phase 2 | 1 |
| 113 | U | 3 / 4 | INFREQ2 | Input Frequency Hz Phase 3 | 1 |
| 114 | U | 3 / 4 | CNT_PF | Powerfail Counter | 1 |
| 115 | U | 3 / 4 | Alarm Battery Bad | 1 = active; 0 = not active | 1 |
| 116 | U | 3 / 4 | Alarm: On Battery | 1 = active; 0 = not active | 1 |
| 117 | U | 3 / 4 | Alarm: Battery Low | 1 = active; 0 = not active | 1 |
| 118 | U | 3 / 4 | Alarm: Battery Depleted | 1 = active; 0 = not active | 1 |
| 119 | U | 3 / 4 | Alarm: Over temperature | 1 = active; 0 = not active | 1 |
| 120 | U | 3 / 4 | Alarm: Input Bad | 1 = active; 0 = not active | 1 |
| 121 | U | 3 / 4 | Alarm: Output Bad | 1 = active; 0 = not active | 1 |
| 122 | U | 3 / 4 | Alarm: Output Overload | 1 = active; 0 = not active | 1 |
| 123 | U | 3 / 4 | Alarm: On Bypass | 1 = active; 0 = not active | 1 |
| 124 | U | 3 / 4 | Alarm: Bypass Bad | 1 = active; 0 = not active | 1 |
| 125 | U | 3 / 4 | Alarm: Output Off as requested. | 1 = active; 0 = not active | 1 |
| 126 | U | 3 / 4 | Alarm: UPS Off as requested. | 1 = active; 0 = not active | 1 |
| 127 | U | 3 / 4 | Alarm: Charger Failed | 1 = active; 0 = not active | 1 |
| 128 | U | 3 / 4 | Alarm: UPS Output Off | 1 = active; 0 = not active | 1 |
| 129 | U | 3 / 4 | Alarm: UPS System Off | 1 = active; 0 = not active | 1 |
| 130 | U | 3 / 4 | Alarm: Fan Failure | 1 = active; 0 = not active | 1 |
| 131 | U | 3 / 4 | Alarm: fuse failure | 1 = active; 0 = not active | 1 |
| 132 | U | 3 / 4 | Alarm: general fault | 1 = active; 0 = not active | 1 |
| 133 | U | 3 / 4 | Alarm: diagnose test failed | 1 = active; 0 = not active | 1 |
| 134 | U | 3 / 4 | Alarm: communication lost | 1 = active; 0 = not active | 1 |
| 135 | U | 3 / 4 | Alarm: awaiting power | 1 = active; 0 = not active | 1 |
| 136 | U | 3 / 4 | Alarm: shutdown pending | 1 = active; 0 = not active | 1 |
| 137 | U | 3 / 4 | Alarm: shutdown imminent | 1 = active; 0 = not active | 1 |
| 138 | U | 3 / 4 | Alarm: test in progress | 1 = active; 0 = not active | 1 |
| 139 | U | 3 / 4 | PXWARN | 2 | |
| 141 | U | 3 / 4 | FAULT CODE 1 | 1 | |
| 142 | U | 3 / 4 | FAULT CODE 2 | 1 | |
| 143 | U | 3 / 4 | FAULT CODE 3 | 1 | |
| 144 | U | 3 / 4 | FAULT CODE 4 | 1 | |
| 145 | U | 3 / 4 | BADBATTBLOCK 1 | 1 | |
| 146 | U | 3 / 4 | BADBATTBLOCK 1 | 1 | |
| 147 | U | 3 / 4 | BADBATTBLOCK 1 | 1 | |
| 148 | U | 3 / 4 | BADBATTBLOCK 1 | 1 | |
| 149 | U | 3 / 4 | BADBATTBLOCK 1 | 1 | |
| 150 | U | 3 / 4 | BADBATTBLOCK 1 | 1 |