| Address | Type | Function | Name | Description | Length |
| 100 | U | 03. Apr | INVOLT | Input Voltage | 1 |
| 101 | U | 03. Apr | OUTPUTVOLT | Output Voltage | 1 |
| 102 | U | 03. Apr | BATTVOLT | Battery Voltage | 1 |
| 103 | U | 03. Apr | OUTPUTCURR | Output Current | 1 |
| 104 | U | 03. Apr | LOADPERC | Load (%) | 1 |
| 105 | U | 03. Apr | OUTPUTPOW | Output Power in W | 1 |
| 106 | U | 03. Apr | KVA | KVA | 1 |
| 107 | U | 03. Apr | FREQUENCY | Frequency | 1 |
| 108 | U | 03. Apr | CS141UPSSTAT | CS141 UPS Status | 1 |
| 109 | U | 03. Apr | Alarm: Battery Bad | 1 = active; 0 = not active | 1 |
| 110 | U | 03. Apr | Alarm: On Battery | 1 = active; 0 = not active | 1 |
| 111 | U | 03. Apr | Alarm: Battery Low | 1 = active; 0 = not active | 1 |
| 112 | U | 03. Apr | Alarm: Battery Depleted | 1 = active; 0 = not active | 1 |
| 113 | U | 03. Apr | Alarm: Overtemperature | 1 = active; 0 = not active | 1 |
| 114 | U | 03. Apr | Alarm: Input Bad | 1 = active; 0 = not active | 1 |
| 115 | U | 03. Apr | Alarm: Output Bad | 1 = active; 0 = not active | 1 |
| 116 | U | 03. Apr | Alarm: Output Overload | 1 = active; 0 = not active | 1 |
| 117 | U | 03. Apr | Alarm: On Bypass | 1 = active; 0 = not active | 1 |
| 118 | U | 03. Apr | Alarm: Bypass Bad | 1 = active; 0 = not active | 1 |
| 119 | U | 03. Apr | Alarm: Ouput Off As Requested | 1 = active; 0 = not active | 1 |
| 120 | U | 03. Apr | Alarm: UPS Off As Requested | 1 = active; 0 = not active | 1 |
| 121 | U | 03. Apr | Alarm: Charger Failed | 1 = active; 0 = not active | 1 |
| 122 | U | 03. Apr | Alarm: UPS Output Off | 1 = active; 0 = not active | 1 |
| 123 | U | 03. Apr | Alarm: UPS System Off | 1 = active; 0 = not active | 1 |
| 124 | U | 03. Apr | Alarm: Fan Failure | 1 = active; 0 = not active | 1 |
| 125 | U | 03. Apr | Alarm: Fuse Failure | 1 = active; 0 = not active | 1 |
| 126 | U | 03. Apr | Alarm: General Fault | 1 = active; 0 = not active | 1 |
| 127 | U | 03. Apr | Alarm: Diagnosis Test Failed | 1 = active; 0 = not active | 1 |
| 128 | U | 03. Apr | Alarm: Communication Lost | 1 = active; 0 = not active | 1 |
| 129 | U | 03. Apr | Alarm: Awaiting Power | 1 = active; 0 = not active | 1 |
| 130 | U | 03. Apr | Alarm: Shutdown Pending | 1 = active; 0 = not active | 1 |
| 131 | U | 03. Apr | Alarm: Shutdown Imminent | 1 = active; 0 = not active | 1 |
| 132 | U | 03. Apr | Alarm: Test In Progress | 1 = active ; 0 = not active | 1 |
| 133 | U | 03. Apr | AUX Port 1 | 1 = active (high) ; 0 = not active (low) | 1 |
| 134 | U | 03. Apr | AUX Port 2 | 1 = active (high) ; 0 = not active (low) | 1 |
| 135 | U | 03. Apr | AUX Port 3 | 1 = active (high) ; 0 = not active (low) | 1 |
| 136 | U | 03. Apr | AUX Port 4 | 1 = active (high) ; 0 = not active (low) | 1 |
| 137 | U | 03. Apr | SensorManager/SMTH_COM, Sensor 1 | Analog Value | 1 |
| 138 | U | 03. Apr | SensorManager/SMTH_COM, Sensor 2 | Analog Value | 1 |
| 139 | U | 03. Apr | SensorManager/Sensor 3 | Analog Value | 1 |
| 140 | U | 03. Apr | SensorManager/Sensor 4 | Analog Value | 1 |
| 141 | U | 03. Apr | SensorManager/Sensor 5 | Analog Value | 1 |
| 142 | U | 03. Apr | SensorManager/Sensor 6 | Analog Value | 1 |
| 143 | U | 03. Apr | SensorManager/Sensor 7 | Analog Value | 1 |
| 144 | U | 03. Apr | SensorManager/Sensor 8 | Analog Value | 1 |
| 145 | U | 03. Apr | Result of the last Battery Test | Value 3 = Battery Test passed, Value 4 = Battery Test failed | 1 |