| Address | Type | Function | Name | Description | Length |
| 97 | U | 3 / 4 | OUTPUT_VOLT0 | Output Voltage Phase 1 in V | 1 |
| 98 | U | 3 / 4 | OUTPUT_VOLT1 | Output Voltage Phase 2 in V | 1 |
| 99 | U | 3 / 4 | OUTPUT_VOLT2 | Output Voltage Phase 3 in V | 1 |
| 100 | U | 3 / 4 | OUTPOWER0 | Outpower Phase 1 % | 1 |
| 101 | U | 3 / 4 | OUTPOWER1 | Outpower Phase 2 % | 1 |
| 102 | U | 3 / 4 | OUTPOWER2 | Outpower Phase 3 % | 1 |
| 103 | U | 3 / 4 | BATTCAP | Battery Capacity % | 1 |
| 104 | U | 3 / 4 | INVOLT0 | Input Voltage Phase 1 V | 1 |
| 105 | U | 3 / 4 | INVOLT1 | Input Voltage Phase 2 V | 1 |
| 106 | U | 3 / 4 | INVOLT2 | Input Voltage Phase 3 V | 1 |
| 107 | U | 3 / 4 | TEMPDEG | Temperature C° | 1 |
| 108 | U | 3 / 4 | AUTONOMTIME | Autonomy Time minutes | 1 |
| 109 | U | 3 / 4 | STATUS (e. g. UPS normal = “4”, Powerfail = “12”, Battery test running = “68”, Bypass = “5” ) | UPS Status (ASCII HEX) Please note UPSMAN status bytes table below | 1 |
| 110 | U | 3 / 4 | BATTVOLT | Battery Voltage V | 1 |
| 111 | U | 3 / 4 | INFREQ0 | Input Frequency Hz Phase 1 | 1 |
| 112 | U | 3 / 4 | INFREQ1 | Input Frequency Hz Phase 2 | 1 |
| 113 | U | 3 / 4 | INFREQ2 | Input Frequency Hz Phase 3 | 1 |
| 114 | U | 3 / 4 | CNT_PF | Powerfail Counter | 1 |
| 115 | U | 3 / 4 | (SNMPALARMS&0x1) | Alarm Battery Bad | 1 |
| 116 | U | 3 / 4 | (SNMPALARMS&0x2)>>1 | Alarm: On Battery | 1 |
| 117 | U | 3 / 4 | (SNMPALARMS&0x4)>>2 | Alarm: Battery Low | 1 |
| 118 | U | 3 / 4 | (SNMPALARMS&0x8)>>3 | Alarm: Battery Depleted | 1 |
| 119 | U | 3 / 4 | (SNMPALARMS&0x10)>>4 | Alarm: Over temperature | 1 |
| 120 | U | 3 / 4 | (SNMPALARMS&0x20)>>5 | Alarm: Input Bad | 1 |
| 121 | U | 3 / 4 | (SNMPALARMS&0x40)>>6 | Alarm: Output Bad | 1 |
| 122 | U | 3 / 4 | (SNMPALARMS&0x80)>>7 | Alarm: Output Overload | 1 |
| 123 | U | 3 / 4 | (SNMPALARMS&0x100)>>8 | Alarm: On Bypass | 1 |
| 124 | U | 3 / 4 | (SNMPALARMS&0x200)>>9 | Alarm: Bypass Bad | 1 |
| 125 | U | 3 / 4 | (SNMPALARMS&0x400)>>10 | Alarm: Output Off as requested. | 1 |
| 126 | U | 3 / 4 | (SNMPALARMS&0x800)>>11 | Alarm: UPS Off as requested. | 1 |
| 127 | U | 3 / 4 | (SNMPALARMS&0x1000)>>12 | Alarm: Charger Failed | 1 |
| 128 | U | 3 / 4 | (SNMPALARMS&0x2000)>>13 | Alarm: UPS Output Off | 1 |
| 129 | U | 3 / 4 | (SNMPALARMS&0x4000)>>14 | Alarm: UPS System Off | 1 |
| 130 | U | 3 / 4 | (SNMPALARMS&0x8000)>>15 | Alarm: Fan Failure | 1 |
| 131 | U | 3 / 4 | (SNMPALARMS&0x10000)>>16 | Alarm: fuse failure | 1 |
| 132 | U | 3 / 4 | (SNMPALARMS&0x20000)>>17 | Alarm: general fault | 1 |
| 133 | U | 3 / 4 | (SNMPALARMS&0x40000)>>18 | Alarm: diagnose test failed | 1 |
| 134 | U | 3 / 4 | (SNMPALARMS&0x80000)>>19 | Alarm: communication lost | 1 |
| 135 | U | 3 / 4 | (SNMPALARMS&0x100000)>>20 | Alarm: awaiting power | 1 |
| 136 | U | 3 / 4 | (SNMPALARMS&0x200000)>>21 | Alarm: shutdown pending | 1 |
| 137 | U | 3 / 4 | (SNMPALARMS&0x400000)>>22 | Alarm: shutdown imminent | 1 |
| 138 | U | 3 / 4 | (SNMPALARMS&0x800000)>>23 | Alarm: test in progress | 1 |
| 139 | U | 3 / 4 | AUX1STATE | AUX Port 1 1 = active (high), 0 = not active (low) | 1 |
| 140 | U | 3 / 4 | AUX2STATE | AUS Port 2 1 = active (high), 0 = not active (low) | 1 |
| 141 | U | 3 / 4 | AUX3STATE | AUX Port 3 1 = active (high), 0 = not active (low) | 1 |
| 142 | U | 3 / 4 | AUX4STATE | AUS Port 4 1 = active (high), 0 = not active (low) | 1 |
| 143 | U | 3 / 4 | TEMP1 | SensorManager/SM_T_H_COM Analog Value | 1 |
| 144 | U | 3 / 4 | TEMP2 | SensorManager/SM_T_H_COM Analog Value | 1 |
| 145 | U | 3 / 4 | TEMP3 | SensorManager Analog Value | 1 |
| 146 | U | 3 / 4 | TEMP4 | SensorManager Analog Value | 1 |
| 147 | U | 3 / 4 | TEMP5 | SensorManager Analog Value | 1 |
| 148 | U | 3 / 4 | TEMP6 | SensorManager Analog Value | 1 |
| 149 | U | 3 / 4 | TEMP7 | SensorManager Analog Value | 1 |
| 150 | U | 3 / 4 | TEMP8 | SensorManager Analog Value | 1 |
| 151 | U | 3 / 4 | (MODULEMASK&0xFFFF) | Please Contact Centiél | 1 |
| 152 | U | 3 / 4 | (MODULEMASK&0xFFFF0000)>>16 | Please Contact Centiél | 1 |
| 153 | U | 3 / 4 | (RAWSTATEB&0xFFFF) | Statusbit, for details please contact Centiél | 1 |
| 154 | U | 3 / 4 | (RAWSTATEB&0xFFFF0000)>>16 | Statusbit, for details please contact Centiél | 1 |
| 155 | U | 3 / 4 | (RAWSTATEA&0xFFFF) | Statusbit, for details please contact Centiél | 1 |
| 156 | U | 3 / 4 | (RAWSTATEA&0xFFFF0000)>>16 | Statusbit, for details please contact Centiél | 1 |
| 157 | U | 3 / 4 | (RAWSTATED&0xFFFF) | Statusbit, for details please contact Centiél | 1 |
| 158 | U | 3 / 4 | (RAWSTATED&0xFFFF0000)>>16 | Statusbit, for details please contact Centiél | 1 |
| 159 | U | 3 / 4 | EX_OUT_WATT0 | Output Power Phase 1 [W] | 1 |
| 160 | U | 3 / 4 | EX_OUT_WATT1 | Output Power Phase 2 [W] | 1 |
| 161 | U | 3 / 4 | EX_OUT_WATT2 | Output Power Phase 3 [W] | 1 |
| 162 | U | 3 / 4 | CONCE_IDENT | String Identifying the UPS | 1 |
| 194 | U | 3 / 4 | CONCE_VERSION | UPS Firmware Version | 1 |
| 210 | U | 3 / 4 | EX_BYP_VOLT0 | Bypass Voltage Phase 1 in V | 1 |
| 211 | U | 3 / 4 | EX_BYP_VOLT1 | Bypass Voltage Phase 2 in V | 1 |
| 212 | U | 3 / 4 | EX_BYP_VOLT2 | Bypass Voltage Phase 3 in V | 1 |
| 213 | U | 3 / 4 | EX_BYP_FREQ0 | Bypass Frequency Phase 1 in [Hz] | 1 |
| 214 | U | 3 / 4 | EX_BYP_FREQ1 | Bypass Frequency Phase 2 in [Hz] | 1 |
| 215 | U | 3 / 4 | EX_BYP_FREQ2 | Bypass Frequency Phase 3 in [Hz] | 1 |
| 216 | U | 3 / 4 | EX_OUT_CURR0 | Output Current Phase 1 [A] | 1 |
| 217 | U | 3 / 4 | EX_OUT_CURR1 | Output Current Phase 2 [A] | 1 |
| 218 | U | 3 / 4 | EX_OUT_CURR2 | Output Current Phase 3 [A] | 1 |
| 219 | U | 3 / 4 | OUTFREQ0 | Output Frequency Phase 1 in [Hz] | 1 |
| 220 | U | 3 / 4 | OUTFREQ1 | Output Frequency Phase 2 in [Hz] | 1 |
| 221 | U | 3 / 4 | OUTFREQ2 | Output Frequency Phase 3 in [Hz] | 1 |
| 222 | U | 3 / 4 | EX_BATT_CURRPOS | Positive battery current [A] | 1 |
| 223 | U | 3 / 4 | EX_BATT_CURRNEG | Negative battery current [A] | 1 |
| 224 | U | 3 /4 | OUTPUT_KHW | True Output Power Current In kilowatt-hour | 1 |
| 225 | U | 3 / 4 | INCURR0 | Input Current Phase 1 in A | 1 |
| 226 | U | 3 / 4 | INCURR1 | Input Current Phase 2 in A | 1 |
| 227 | U | 3 / 4 | INCURR 2 | Input Current Phase 3 in A | 1 |
| 228 | U | 3 / 4 | EX_OUT_VA0/1000 | Output Apparent Power Phase 1 [kVA] | 1 |
| 229 | U | 3 / 4 | EX_OUT_VA1/1000 | Output Apparent Power Phase 2[kVA] | 1 |
| 230 | U | 3 / 4 | EX_OUT_VA2/1000 | Output Apparent Power Phase 3[kVA] | 1 |
| 231 | U | 3 / 4 | EX_OUT_WATT0/1000 | Output Power Phase 1 [kW] | 1 |
| 232 | U | 3 / 4 | EX_OUT_WATT1/1000 | Output Power Phase 2 [kW] | 1 |
| 233 | U | 3 / 4 | EX_OUT_WATT2/1000 | Output Power Phase 3 [kW] | 1 |