Note: all values are Integer (int). S=Signed U=Unsigned
| Register | Type | Function | Name | Coefficient | Unit |
| 97 | U | 3 / 4 | Output Voltage L1 | 1 | V |
| 98 | U | 3 / 4 | Output Voltage L2 | 1 | V |
| 99 | U | 3 / 4 | Output Voltage L3 | 1 | V |
| 100 | U | 3 / 4 | Output Power L1 | 1 | % |
| 101 | U | 3 / 4 | Output Power L2 | 1 | % |
| 102 | U | 3 / 4 | Output Power L3 | 1 | % |
| 103 | U | 3 / 4 | Battery Capacity | 1 | % |
| 104 | U | 3 / 4 | Input Voltage L1 | 1 | V |
| 105 | U | 3 / 4 | Input Voltage L2 | 1 | V |
| 106 | U | 3 / 4 | Input Voltage L3 | 1 | V |
| 107 | U | 3 / 4 | Unit Temperature | 1 | C° |
| 108 | U | 3 / 4 | Autonomy Time | 1 | minutes |
| 109 | U | 3 / 4 | UPS STATUS (e. g. UPS normal = “4”, Powerfail = “12”, Battery test running = “68”, Bypass = “5”) | UPS Status (ASCII HEX) Please note UPSMAN status bytes table below | Status |
| 110 | U | 3 / 4 | Battery Voltage | 1 | V |
| 111 | U | 3 / 4 | Input Frequency L1 | 1 | Hz |
| 112 | U | 3 / 4 | Input Frequency L2 | 1 | Hz |
| 113 | U | 3 / 4 | Input Frequency L3 | 1 | Hz |
| 114 | U | 3 / 4 | Powerfail Counter | 1 | Counter |
| 115 | U | 3 / 4 | Alarm Battery Bad | 0: No 1: Yes | Status |
| 116 | U | 3 / 4 | Alarm: On Battery | 0: No 1: Yes | Status |
| 117 | U | 3 / 4 | Alarm: Battery Low | 0: No 1: Yes | Status |
| 118 | U | 3 / 4 | Alarm: Battery Depleted | 0: No 1: Yes | Status |
| 119 | U | 3 / 4 | Alarm: Over temperature | 0: No 1: Yes | Status |
| 120 | U | 3 / 4 | Alarm: Input Bad | 0: No 1: Yes | Status |
| 121 | U | 3 / 4 | Alarm: Output Bad | 0: No 1: Yes | Status |
| 122 | U | 3 / 4 | Alarm: Output Overload | 0: No 1: Yes | Status |