Issue
After uploading a firmware update file to the CS141 and starting the update, you may experience either of the following:
- The CS141 repeatedly requests administrator credentials. After each entry, the progress bar advances by approximately 1% before the prompt appears again.
- The update reaches approximately 90–100%, then repeatedly requests administrator credentials.
In both cases, the progress bar eventually reaches 100% and the CS141 reboots, but the previous firmware version remains installed.
Troubleshooting steps
Changing the administrator password before retrying the update may resolve this issue.
- Log in to the CS141 as an administrator.
-
Go to System > Users and change the password for the admin account. Save your changes.
- Log out of the CS141.
- Log back in using the new administrator password.
- Restart the firmware update. If prompted for administrator credentials, use the new password.
- Once the update has completed and the CS141 has rebooted, log in and verify that the new firmware version is installed.
After a successful update, you can change the administrator password back to your previous password if required.
If the issue persists
Contact support@generex.de for further assistance. Include your current firmware version, the version you are trying to install, and a brief description of when the credential prompts appear.